Doosan Infracore P126TI-II Genset

Description

Doosan Infracore engines for power generation are built for maximum power output and durability. The engines are installed in prime and standby generators in the world.

 

Features

The power ratings of Emergency Standby and Prime are in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046.

STANDBY POWER RATING is applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. A standby rated engine should be sized for a maximum of an 80% average load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating.

PRIME POWER RATING is available for an unlimited number of hours per year in variable load application. Variable load should not exceed a 70% average of the Prime Power rating during any operating period of 250 hours. The Total operating time at 100% Prime Power shall not exceed 500 hours per year. A 10% overload capability is available for a period of 1 hour withing a 12 hour period of operation. Total operating time at the 10% overload power shall not exceed 25 hous per year.

 

View PDF Spec Sheet -> click to download

 
   
 
 



 
 

 
 
 
 
 


Social Networks

Copyright © ELEGEN™ / Caco Trading (Pty) Ltd

 


Head Office:
23-24 Mountjoy Street
Wilbart, Bedfordview, 1401
Gauteng, South Africa

Responsive Web Design & Online Marketing - www.itdev.co.za